Description
Item | GSL48200 | Remark |
Combination Method | 16S34P | 48 |
Rated Capacity | 200Ah | Standard discharge after Standard
charge(package) |
Factory Voltage | 51.2V | Mean Operation Voltage |
Voltage at end of Discharge | 46V | Discharge Cut-off Voltage |
Charge Voltage | 56V | Charge Cut-off Voltage |
Internal Impedance | ≤55.0mΩ | Internal resistance measured at AC
1KHZ after 50% chargeThe measure must uses the new batteries that within one week after shipment and cycles less than 5 times |
Standard charge | Constant Current 50A
Constant Voltage see No.5 0.02CA cut-off |
Charge time : Approx 2.5 h |
Maximum Continuous Charge Current | 100A | |
Standard Discharge | end voltage see NO.4 | |
Maximum Continuous Discharge Current | 120A | 100A when 0ºC>T≥-20ºC |
Operation Temperature Range | Charge: 0~45℃ | 60±25%R.H.
Bare Cell |
Discharge: -20~55℃ | ||
Storage Temperature Range | Less than 12 months : -10~35℃ | 60±25%R.H.
at the shipment state |
Less than 3 months: -10~45℃ | ||
Less than 7 day : -20~65℃ | ||
Dimensions | 720*480*222.2mm | Include Bracket |
Weight | Approx :102.5 kg | |
BMS Port | CANBUS/RS485 | |
BMS Support | 16PCS Parallel connection | 160KWH at max |